RBI FUTERA III Series Instruction Manual Page 12

  • Download
  • Add to my manuals
  • Print
  • Page
    / 80
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 11
12
Version 3.37 – Control Board Manual used for Futera III, Futera Fusion and Futera XLF
V
ers
i
on
3
.
37
C
ontro
l
B
oar
d
M
anua
l
use
d
f
or
F
utera
III
,
F
utera
F
us
i
on an
d
F
utera
XLF
Figure 9 Boiler System Response 1
(2) MB/MW 500s, (3) MB/MW 1250s
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0 1,000,000 2,000,000 3,000,000 4,000,000 5,000,000
I
n
p
u
t,
%
System Load, Btu/Hr
Blr 1+2+3 (2250 MBTU)
Blr 1+2+3+4 (3500 MBTU)
Blr 1+2+3+4+5 (4750 MBTU)
When running non condensing boilers at low input
rates, the risk of condensing should be considered.
e Boiler System Response 1 chart illustrates how each boiler (in
the example) is brought on and  res to 60%, drops to a lower  re
rate and then adds the next boiler (vertical dashed lines). Once all
boilers are  ring, the modulation is released allowing all boilers to
re to 100%.
Now, if (1) MB/MW 500 (one of the MB/MW 500s was brought
o ine) were used with (3) MB/MW 1250s and the Mod-Max is
set to 60%, the MB/MW 500 would  re to 300 MBTUs and wait
for the MB/MW 1250 (Boiler System Response 2 graph). Now,
the minimum input rate would be 312M (MB/MW 1250) + the
125M (MB/MW 500) (already running, but dropped to low  re
when the MB/MW 1250  red), the total being 437M. With a 60%
MOD-MAX clamp, there would be 137 MBTUS more than needed
and added to the system when the MB/MW 1250  red.
e PID algorithm would then compensate for the discontinuity
(bump) in BTUs and the MB/MW 1250 could shut o (short
cycle).
is discontinuity is observed in the graph below, (Boiler System
Response 2) where the jump from the MB/MW 500 @60% to the
ring of the MB/MW 1250 is apparent.
Figure 10 Boiler System Response 2
(1) MB/MW 500, (3) MB/MW 1250, 60% Mod-Max
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0 1,000,000 2,000,000 3,000,000 4,000,000 5,000,000
I
n
p
u
t,
%
System Load, Btu/Hr
Blr 1+2 (1750 MBTU)
Blr 1+2+3 (4250 MBTU)
Blr 1+2+3 (3000 MBTU)
To correct this would require the MB/MW 500 to set the MOD-
MAX to roughly 90% (Boiler System Response 3: not as e cient
as it could be when using CB/CW Fusion boilers) in order to have
a linear BTU transfer when the MB/MW 1250 is added ( red).
Figure 11 Boiler System Response 3
(1) MB/MW 500, (3) MB/MW 1250, 60% Mod-Max
0.00
0.10
0.20
0.30
0.40
0.50
0.60
0.70
0.80
0.90
1.00
0 1,000,000 2,000,000 3,000,000 4,000,000 5,000,000
I
n
p
u
t,
%
System Load, Btu/Hr
Blr 1+2 (1750 MBTU)
Blr 1+2+3 (4250 MBTU)
Blr 1+2+3 (3000 MBTU)
An MB/MW 500 running with a MB/MW 1250 may not be an
optimal choice unless (2) MB/MW 500s are used in the Priority1
set or (3) MB/MW 500s and one is allowed to be taken o ine.
A system employing this redundancy where (1) is allowed to be
taken o ine is listed in the MIXED BOILER SYSTEM chart.
is system uses (3) MB/MW 500s and (3) MB/MW 1500s. Two
of the MB/MW 500s are treated as one when adding the min inputs
of the Priority1 set.
Page view 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 79 80

Comments to this Manuals

No comments